Phoenix - UK 10 N - 3005073 Straight-through terminal block
1
  • Phoenix - UK 10 N - 3005073 Straight-through terminal block
2
views: 251

Phoenix - UK 10 N - 3005073 Straight-through terminal block

Rate:
0.0000/5

( 0 reviews )

Item NO.: V000123 MOQ: 0
Weight:    0kgs
Package Size:  
 Price:
$0.00
 Qty:
      $0.00
 Shipping:   Calculate Shipping Cost

Phoenix - UK 10 N - 3005073 Straight-through terminal block

NQ


Number of layers 1
Number of connections 2
Electrical potential 1
Rated cross section 10 mm²
Color Gray
Insulation material PA
Flame retardant class according to UL 94 V0
Rated surge voltage 8 kV
Pollution class 3
Overvoltage class III
Insulation material group I
Maximum power consumption under rated conditions * 1.82 W
*Maximum load current 76 A (when connecting conductors with a cross-sectional area of 16 mm2)
Rated current IN 57 A
Rated voltage UN 800 V
Open side panel Yes
Shock test specification DIN EN 60529 (VDE 0470-1):2000-09
Protection against back of hand contact Guaranteed
Finger touch protection Guaranteed
Surge voltage test results Pass test
Impulse withstand voltage test set point 9.8 kV
Power frequency withstand voltage test result Passed test
High power frequency withstand voltage set point 2 kV
(Mechanical stability test results at junction points (5x wire connections) Passed
Bending test results Passed
Bending test rotation speed 10 rpm
Bending test 135
Bend test wire cross section / weight 0.5 mm² / 0.3 kg
  10 mm² / 2 kg
  16 mm² / 2.9 kg
Tensile force test results Pass test
Wire cross-section tensile force test 0.5 mm²
Traction force set point 20 N
Wire cross-sectional tensile force test 10 mm²
Traction force set point 90 N
Cross-sectional tension test 16 mm²
Traction force set point 100 N
Fastening test results on bracket Pass test
Fastening on end plates NS 32/NS 35
Setpoint 5 N
Voltage drop test result Passes the test
Required, voltage drop ≤ 3.2 mV
Temperature rise test result Passed test
Short-circuit stability test Passed test
Short-circuit test with cross-sectional conductors 10 mm²
Short-time current 1.2 kA
Short-circuit test with cross-sectional conductors 16 mm²
Short-time current 1.92 kA
Thermal test results Passed the test
Verification of thermal characteristics (needle flame test) Effective withstand period 30 s
Test results for oscillation, broadband noise Passed test
Test specification, oscillation, broadband noise DIN EN 50155 (VDE 0115-200):2008-03
Test spectrum Class 1, service life test class B, on the vehicle body
Test frequency f1 = 5 Hz to f2 = 150 Hz
ASD class 1.857 (m/s2)2/Hz
Acceleration 0,8 g
Test cycle per axis 5 h
Test directions X-, Y- and Z-axes
Impact test results Pass test
Test specification, impact test DIN EN 50155 (VDE 0115-200):2008-03
Type of impact Half-sine
Acceleration 5 g
Duration of impact 30 ms
Number of shocks per direction 3
Test direction X-, Y- and Z-axis (positive and negative)
Relative temperature index of the insulating material (electrical, UL 746 B) 130 °C
Temperature index of the insulating material (DIN EN 60216-1 (VDE 0304-21)) 130 °C
Static insulating material applications at low temperatures -60 °C
Fire resistance of railroad vehicles (DIN 5510-2) Passing the test
Flame color test method (DIN EN 60695-11-10) V0
Oxygen index (DIN EN ISO 4589-2) >32 %
NF F16-101, NF F10-102 Class I 2
NF F16-101, NF F10-102 Class F 2
Surface flammability NFPA 130 (ASTM E 162) Passed
Smoke Specific Optical Density NFPA 130 (ASTM E 662) Passed
Smoke Toxicity NFPA 130 (SMP 800C) Passed
Calorimetric heat release NFPA 130 (ASTM E 1354) 28 MJ/kg
Fire protection for railroad vehicles (DIN EN 45545-2) R22 HL 1 - HL 3
Fire protection for railroad vehicles (DIN EN 45545-2) R23 HL 1 - HL 3
Fire protection for railroad vehicles (DIN EN 45545-2) R24 HL 1 - HL 3
Fire protection for railroad vehicles (DIN EN 45545-2) R26 HL 1 - HL 3

 