ZZC
Product * * * Name of SIRIUS
Product name: The contactor
Product Type Name 3RT5
Comprehensive technical data
Structural size S2 of the contactor
Product extension auxiliary switch Yes
Insulation voltage measurement value is 690 V
Pollution degree 3
Impact voltage resistance measurement value of 6 kV
The * * * large allowable voltage for safe isolation meets EN 60947-1 400 V between the coil and the main contact
Impact is resistant to square wave impact
● AC at 10g / 5 ms and 5g / 10 ms
When resistant to impact-resistant sinusoidal impact
● AC at 15g / 5 ms, 8g / 10 ms
Mechanical service life (conversion cycle)
Typical 10 000 000 for the ● contactor
● Typical 10 000 000 for contactor with auxiliary switch block
RoHS Directive (date) 03 / 01 / 2017
ambient condition
Installation height is 2 000 m above * * *
ambient temperature
During the ● Run-25.... + 60 °C
● Storage Period-55... + 80 °C
main circuit
Pole are used for main circuit 3
Normally open contacts number is used for primary contacts 3
Number of normally closed contacts is used for primary contact 0
working current
● AC-1 when: * * * is 690 V high
- -Determination value of 60 A at an ambient temperature of 40 °C
-Determination of 55 A at an ambient temperature of 60 °C
When the ● AC-3
— 40 A as measured at 400 V
— 24 A as measured at 690 V
When the connected wire section is AC-1 in the main circuit
● 60 °C when licensed * * * small value of 16 mm²
● 40 °C when licensed * * * small value of 16 mm²
The operating current is about 200,000 operating cycles of AC-4
Measurement value of 18.5 A at ● 400 V
12.6 A was measured at ● 690 V
power rating
When the ● AC-1
— 22 kW was measured at 60 °C at 230 V
— 38 kW was measured at 60 °C at 400 V
— 66 kW at 60 °C at 690 V
When the ● AC-3
-11 kW at 230 V
-18.5 kW at 400 V
— Devalue of 22 V at 690 V
Rated power of about 200,000 operation cycle AC-4
The measurement value was 9.5 kW at ● 400 V
The measurement value was 11.4 kW at ● 690 V
No-load operation frequency
5 000 1 / h at ● AC
switching frequency
* * * Large value of 1 200 1 / h at ● AC-1
* * * Large value of 1 000 1 / h at ● AC-3
● AC-4 * * * Large value of 300 1 / h