Product or component type : Miniature circuit-breaker
Device short name : IC60N
Poles description : 2P
Number of protected poles : 2
[In] rated current : 25 A
Network type : DCAC
Trip unit technology : Thermal-magnetic
Curve code : C
Breaking capacity : 6 kA Icu conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz10 kA Icu conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz20 kA Icu conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz6000 A Icn conforming to EN/IEC 60898-1 - 400 V AC 50/60 Hz36 kA Icu conforming to EN/IEC 60947-2 - 12...60 V AC 50/60 Hz10 kA Icu conforming to EN/IEC 60947-2 - 36 kA Icu conforming to EN/IEC 60947-2 - 100...133 V AC 50/60 Hz
Utilisation category : Category A conforming to EN 60947-2Category A conforming to IEC 60947-2
Suitability for isolation : Yes conforming to EN 60947-2Yes conforming to IEC 60947-2Yes conforming to EN 60898-1Yes conforming to IEC 60898-1
[Ics] rated service breaking capacity : 6000 A 100 % x Icu conforming to IEC 60898-1 - 400 V AC 50/60 Hz10 kA 100 % x Icu conforming to IEC 60947-2 - 72...125 V DC10 kA 100 % x Icu conforming to EN 60947-2 - 72...125 V DC6000 A 100 % x Icu conforming to EN 60898-1 - 400 V AC 50/60 Hz4.5 kA 75 % x Icu conforming to IEC 60947-2 - 440 V AC 50/60 Hz15 kA 75 % x Icu conforming to EN 60947-2 - 220...240 V AC 50/60 Hz7.5 kA 75 % x Icu conforming to EN 60947-2 - 380...415 V AC 50/60 Hz4.5 kA 75 % x Icu conforming to EN 60947-2 - 440 V AC 50/60 Hz15 kA 75 % x Icu conforming to IEC 60947-2 - 220...240 V AC 50/60 Hz7.5 kA 75 % x Icu conforming to IEC 60947-2 - 380...415 V AC 50/60 Hz27 kA 75 % x Icu conforming to IEC 60947-2 - 12...133 V AC 50/60 Hz27 kA 75 % x Icu conforming to EN 60947-2 - 12...133 V AC 50/60 Hz
Limitation class : 3 conforming to EN 60898-13 conforming to IEC 60898-1
[Ui] rated insulation voltage : 500 V AC 50/60 Hz conforming to IEC 60947-2500 V AC 50/60 Hz conforming to EN 60947-2
[Uimp] rated impulse withstand voltage : 6 kV conforming to EN 60947-26 kV conforming to IEC 60947-2
Contact position indicator : Yes
Control type : Toggle
Local signalling : Trip indicator
Mounting mode : Fixed
Mounting support : DIN rail
Comb busbar and distribution block compatibility : YES top or bottom
9 mm pitches : 4
Height : 85 mm
Width : 36 mm
Depth : 78.5 mm
Product weight : 0.25 kg
Colour : White
Mechanical durability : 20000 cycles
Electrical durability : 10000 cycles
Connections - terminals : Single terminal, top or bottom rigid wire(s) 1...25 mm² maxSingle terminal, top or bottom flexible wire(s) 1...16 mm² max