MHH
750-631/000-010
delivery time:2-4 weeks
Counter depth | 16bits |
Encoder connection | A, A/, B, B/, C, C/ (RS-422 inputs) |
Supply current (encoder) max. | 200mA |
Zero impulse (latch) | 16bits |
Quadrature decoder | 4x evaluation |
Voltage range for signal (0) | UABC = 0 V, UABC/ = 5 V; Latch, gate ≤ 5.0 V; External error U ≥ 5.0 V or open input |
Voltage range for signal (1) | UABC = 5 V, UABC/ = 0 V; Latch, gate ≥ 15.0 V; External error U < 0.5 V |
Data width | 1 x 32-bit data, 1 x 8-bit control/status, 1 x 8 bits reserved |
Limit frequency | 1000kHz |
Commands | Reading, setting, activating |
Supply voltage (system) | 5 VDC; via data contacts |
Current consumption (5 V system supply) | 50mA |
Current consumption, field supply (module with no external load) | 10mA |
Isolation | 500 V system/field |
Connection type 1 | Inputs/Outputs |
Solid conductor | 0.08 … 2.5 mm² / 28 … 14 AWG |
Fine-stranded conductor | 0.08 … 2.5 mm² / 28 … 14 AWG |
Strip length | 8 … 9 mm / 0.31 … 0.35 inches |
Width | 24 mm / 0.945 inches |
Height | 100 mm / 3.937 inches |
Depth | 69.8 mm / 2.748 inches |
Depth from upper-edge of DIN-rail | 62.6 mm / 2.465 inches |
Mounting type | DIN-35 rail |
Fire load | 0.174MJ |
Weight | 91.8g |
Ambient temperature (operation) | 0 … +55 °C |
Surrounding air temperature (storage) | -40 … +85 °C |
Protection type | IP20 |
Operating altitude | 0 … 2000 m / 0 … 6562 ft |
Mounting position | horizontal (standing/lying); vertical |
Vibration resistance | per IEC 60068-2-6 |
Shock resistance | 15g per IEC 60068-2-27 |
Permissible H2S contaminant concentration at a relative humidity |
10ppm |
Permissible SO2 contaminant concentration at a relative humidity |
25ppm |