ZLL
LV429830
delivery time:3-4 weeks
range
ComPact
product name
ComPact NSX
range of product
ComPact NSX100...250
device short name
NSX100N
product or component type
Circuit breaker
device application
Motor
Number of poles
3P
protected poles description
3t
[In] rated current
100 A at 65 °C
[Ue] rated operational voltage
690 V AC 50/60 Hz
network type
AC
network frequency
50/60 Hz
suitability for isolation
Yes conforming to EN/IEC 60947-2
utilisation category
Category A
[Icu] rated ultimate short-circuit breaking capacity
85 kA at 240 V AC 50/60 Hz conforming to UL 508
10 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
35 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2
20 kA at 600 V AC 50/60 Hz conforming to UL 508
50 kA at 480 V AC 50/60 Hz conforming to UL 508
36 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
50 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
90 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
Performance level
N 50 kA 415 V AC
trip unit name
Micrologic 2.2 M
trip unit technology
Electronic
trip unit protection functions
LSoI
control type
Toggle
Circuit breaker mounting mode
Fixed
[Ui] rated insulation voltage
800 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage
8 kV
[Ics] rated service short-circuit breaking capacity
10 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
35 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2
36 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2
50 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
50 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
90 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
mechanical durability
50000 cycles
electrical durability
10000 cycles at 690 V In
20000 cycles at 690 V In/2
30000 cycles at 440 V In
50000 cycles at 440 V In/2
mounting support
Backplate
upside connection
Front
downside connection
Front
connection pitch
35 mm
protection type
L : for overload protection (long time)
So : for short time short-circuit protection with fixed delay
I : for instantaneous short-circuit protection
trip unit rating
100 A at 65 °C
motor tripping class
20
10
5
complementary motor protection
Phase unbalance
Long-time pick-up adjustment type Ir (thermal protection)
Adjustable 9 settings
[Ir] long-time protection pick-up adjustment range
50...100 A
Long-time protection delay adjustment type tr
Fixed
[tr] long-time protection delay adjustment range
10 s at 7.2 x Ir for trip class 10
120 s at 1.5 x Ir for trip class 5
20 s at 7.2 x Ir for trip class 20
240 s at 1.5 x Ir for trip class 10
26 s at 6 x Ir for trip class 20
480 s at 1.5 x Ir for trip class 20
5 s at 7.2 x Ir for trip class 5
13.5 s at 6 x Ir for trip class 10
6.5 s at 6 x Ir for trip class 5
thermal memory
20 minutes before and after tripping
Short-time protection pick-up adjustment type Isd
Adjustable 9 settings
[Isd] Short-time protection pick-up adjustment range
5...13 x Ir
Short-time protection delay adjustment type tsd
Fixed
Instantaneous protection pick-up adjustment type Ii
Fixed
[Ii] instantaneous protection pick-up adjustment range
1500 A
earth-leakage protection
Without
zone selective interlocking ZSI
Without
Number of slots for electrical auxiliaries
5 slot(s)
local signalling
Flashing LED (green) for ready to operate
LED 95 % Ith (red) for temperature over set point
Width (W)
105 mm
Height (H)
161 mm
Depth (D)
86 mm
net weight
2.05 kg