Germany EMG (DIM 1000 series electric actuator commissioning steps:
DREHMO (Germany) (SEEUANTRIEBE/ACFUATORS) actuator commissioning steps
◆Press the function key to display the main menu, in the main menu, press the ↑ and ↓ keys to select the Learn Mode menu, and press the function key to enter
menu.
◆Select Parameters (parameters), select Valve (valve) in the public menu, select the menu Closing Direction (setting direction) in the Valve (valve)
◆In Closing Direction, select Coterlowise Open (counterclockwise) or Clowise Open (clockwise) according to the valve type
open direction.
◆Continue to select the Final Position Linmit Sw (final position setting) menu in the Valve (valve) menu, and select the appropriate valve] tripping type in this menu.
◆Press the setting key to enter Local, and learn moba continuously press the l key to select
◆Press Esc to exit to the Learn Mode menu
●Continuously press l to enter Change finol positions (change valve position)
●Press the OK key to enter Clear position close (display position close)
●Continuously press l to enter Set position close
●Press the confirm key to enter the position close 0%========= 100%
● Then press the ↓↑ key to operate the valve [ ] to the actual position required to close, when the actual operating position of the valve [ ] meets the requirements, press the confirm key.
●Open operation steps are the same as above.
●Press the Esc key to exit to the main menu, select Local (local) or Remote (remote control) mode, the setting is completed.
◆The wiring diagram is as follows:
●X2 terminal block: PE2 (U phase), 4 (V phase), 6 (W phase)
●X1 terminal block: 21 and 1 short-circuit, 20 and 2 short-circuit (analog control)
●X1 terminal block: 5 (COM), 6 (open in place), 7 (close in place)
●X1 terminal block: 13 (COM), 14 (fault normally closed), 15 (fault normally open) can be set according to the situation.
●XI terminal block: 23 (+), 24 (-) are 4~20mA feedback signal.
●Xl terminal block: 25(+), 26(-) are 4~20mA command signals.
●XI terminal block: 1 (OV), 2 (stop), 3 (open command), 4 (close command) set according to the situation.

 