HCM
E3SUPS20K3IB
Delivery time:spot goods
Technical Specifications
Output
Max Configurable Power (Watts)
20.0kWatts / 20.0kVA
Output Voltage Distortion
Less than 3 %
Output Frequency (sync to mains)
50 Hz Sync to mains, 60 Hz Sync to mains
Other Output Voltages
220 V, 240 V
Load Crest Factor
3 : 1
Topology
Double conversion online
Overload Operation
10 minutes at 125% and 60 seconds at 150%
Output Voltage THD
< 5.5% at 100% non-linear load
Output Voltage Tolerance
+/- 1.5 %
Input
Input frequency
45 - 65 Hz
Input voltage range for main operations
304 - 477V
Input Total Harmonic Distortion
Less than 5 % for full load
Type of Input Protection Required
Circuit breaker and fuse
Other Input Voltages
380 V, 415 V
Input Power Factor at Full Load
0.99
Batteries & Runtime
Battery type
VRLA
Nominal Battery Voltage
240 V
End of Discharge Maximum Battery Current
54.0A
Battery Slots Empty
3
End of Discharge Battery Voltage
+/- 198 V DC
Maximum Available Short Circuit Current
10kAmps
Efficiency
View Efficiency Graph
Communications & Management
Interface Port(s)
E3S_Parallel, E3S_TempSensor
Physical
Maximum Height
1400MM, 140.0CM
Maximum Width
380MM, 38.0CM
Maximum Depth
907MM, 90.7CM
Net Weight
150.0KG
Shipping weight
158.0KG
Shipping Height
1640MM, 164.0CM
Shipping Width
563MM, 56.3CM
Shipping Depth
1014MM, 101.4CM
Colour
White
Environmental
Operating Temperature
0 - 40 °C
Operating Relative Humidity
0 - 95 (Non-condensing) %
Operating Elevation
0 - 1000.05 meters
Storage Temperature
-25 - 55 °C
Storage Relative Humidity
0 - 95 (Non-condensing) %
Storage Elevation
0 – 15240 meters
Audible noise at 1 meter from surface of unit
60.0dBA
Online thermal dissipation
870.0BTU/hr
Protection Class
IP20
Conformance
Approvals
CE, EAC, IEC 62040-1-1, IEC 62040-2, IEC 62040-3, IEC 62040-4, ISTA 2B, RCM
Sustainable Offer Status
RoHS
Compliant