ZLL
LC1D40M7C
delivery time:in stock
range
TeSys
Range of Product
TeSys D
TeSys Deca
Product or Component Type
Contactor
device short name
LC1D
contactor application
Motor control
Resistive load
utilisation category
AC-1
AC-4
AC-2
AC-3
AC-3e
poles description
3P
[Ue] rated operational voltage
Power circuit <= 690 V AC 25...400 Hz
[Ie] rated operational current
40 A 140 °F (60 °C)) <= 440 V AC AC-3 power circuit
60 A 140 °F (60 °C)) <= 440 V AC AC-1 power circuit
40 A 140 °F (60 °C)) <= 440 V AC AC-3e power circuit
motor power kW
18.5 kW 380...400 V AC 50 Hz AC-3)
22 kW 500 V AC 50 Hz AC-3)
30 kW 660...690 V AC 50 Hz AC-3)
22 kW 1000 V AC 50 Hz AC-3)
22 kW 415 V AC 50 Hz AC-3)
22 kW 440 V AC 50 Hz AC-3)
11 kW 220...230 V AC 50 Hz AC-3)
9 kW 400 V AC 50 Hz AC-4)
18.5 kW 380...400 V AC 50 Hz AC-3e)
22 kW 500 V AC 50 Hz AC-3e)
30 kW 660...690 V AC 50 Hz AC-3e)
22 kW 1000 V AC 50 Hz AC-3e)
22 kW 415 V AC 50 Hz AC-3e)
22 kW 440 V AC 50 Hz AC-3e)
11 kW 220...230 V AC 50 Hz AC-3e)
Maximum Horse Power Rating
3 hp 115 V at AC 60 Hz for 1 phase
5 hp 230/240 V at AC 60 Hz for 1 phase
10 hp 200/208 V at AC 60 Hz for 3 phase
10 hp 230/240 V at AC 60 Hz for 3 phase
30 hp 460/480 V at AC 60 Hz for 3 phase
30 hp 575/600 V at AC 60 Hz for 3 phase
pole contact composition
3 NO
protective cover
With
auxiliary contacts type
Mechanically linked 1 NO + 1 NC IEC 60947-5-1
Mirror contact 1 NC IEC 60947-4-1
auxiliary contact composition
1 NO + 1 NC
[Ui] rated insulation voltage
Control circuit 600 V CSA
Control circuit 600 V UL
Power circuit 600 V CSA
Power circuit 600 V UL
Control circuit 690 V IEC 60947-1
Power circuit 690 V IEC 60947-1
[Uimp] rated impulse withstand voltage
8 kV IEC 60947
overvoltage category
III
[Ith] conventional free air thermal current
10 A 140 °F (60 °C) control circuit
60 A 140 °F (60 °C) power circuit
Irms rated making capacity
800 A 440 V power circuit IEC 60947
140 A AC control circuit IEC 60947-5-1
rated breaking capacity
800 A 440 V power circuit IEC 60947
associated fuse rating
10 A gG control circuit IEC 60947-5-1
80 A gG <= 690 V type 1 power circuit
80 A gG <= 690 V type 2 power circuit
control circuit type
AC 50/60 Hz
coil technology
Without built-in bidirectional peak limiting diode suppressor
control circuit voltage limits
0.3...0.6 Uc -40…158 °F (-40…70 °C) drop-out AC 50/60 Hz
0.8...1.1 Uc -40…140 °F (-40…60 °C) operational AC 50 Hz
0.85...1.1 Uc -40…140 °F (-40…60 °C) operational AC 60 Hz
1...1.1 Uc 140…158 °F (60…70 °C) operational AC 50/60 Hz
power dissipation per pole
5.4 W AC-1
2.4 W AC-3
2.4 W AC-3e
minimum switching current
5 mA control circuit
minimum switching voltage
17 V control circuit
non-overlap time
1.5 ms on de-energisation between NC and NO contacts
1.5 ms on energisation between NC and NO contacts
maximum operating rate
3600 cyc/h 140 °F (60 °C)
inrush power in VA
140 VA 0.75 68 °F (20 °C))
160 VA 0.75 68 °F (20 °C))
hold-in power consumption in VA
13 VA 60 Hz 0.3 68 °F (20 °C))
15 VA 50 Hz 0.3 68 °F (20 °C))
heat dissipation
4…5 W 50/60 Hz control circuit
insulation resistance
> 10 MOhm control circuit
tightening torque
Control circuit 15.05 lbf.in (1.7 N.m) screw clamp terminal flat Ø 6 mm
Control circuit 15.05 lbf.in (1.7 N.m) screw clamp terminal Philips No 2
Power circuit 44.25 lbf.in (5 N.m) screw terminal flat Ø 6 to Ø 8 mm
Control circuit 15.05 lbf.in (1.7 N.m) lugs pozidriv No 2
terminals description ISO n°1
(21-22)NC
(13-14)NO
(A1-A2)CO
Mounting Support
Plate
Rail
mechanical durability
6000000 cycles
safety reliability level
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1
B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
operating altitude
0...9842.52 ft (0...3000 m)
compatibility code
LC1D
standards
EN 60947-4-1
IEC 60947-5-1
CSA C22.2 No 14
EN 60947-5-1
IEC 60947-4-1
UL 508
Product Certifications
LROS (Lloyds register of shipping)
DNV
GL
BV
CCC
RINA
CSA
UL
GOST
UKCA