ZLL
2902991
delivery time:5-7 days
AC operation
Nominal input voltage range
100 V AC ... 240 V AC
Input voltage range
85 V AC ... 264 V AC
Input voltage range AC
85 V AC ... 264 V AC
Voltage type of supply voltage
AC
Inrush current
< 30 A (typ.)
Inrush current integral (I2t)
< 0.4 A2s (typ.)
AC frequency range
50 Hz ... 60 Hz
Frequency range (fN)
50 Hz ... 60 Hz ±10 %
Mains buffering time
> 25 ms (120 V AC)
> 115 ms (230 V AC)
Current consumption
typ. 0.8 A (100 V AC)
typ. 0.4 A (240 V AC)
Nominal power consumption
72.1 VA
Protective circuit
Transient surge protection; Varistor
Power factor (cos phi)
0.47
Typical response time
< 1 s
Input fuse
2 A (slow-blow, internal)
Permissible backup fuse
B6 B10 B16
Recommended breaker for input protection
6 A ... 16 A (Characteristics B, C, D, K)
Efficiency
typ. 87 % (120 V AC)
typ. 88 % (230 V AC)
Output characteristic
HICCUP
Nominal output voltage
24 V DC ±1 %
Nominal output current (IN)
1.25 A (-25 °C ... 55 °C)
Derating
55 °C ... 70 °C (2.5%/K)
Feedback voltage resistance
< 35 V DC
Protection against overvoltage at the output (OVP)
≤ 35 V DC
Control deviation
< 1 % (change in load, static 10 % ... 90 %)
< 2 % (Dynamic load change 10 % ... 90 %, 10 Hz)
< 0.1 % (change in input voltage ±10 %)
Residual ripple
< 60 mVPP (with nominal values)
Short-circuit-proof
yes
Output power
30 W
Maximum no-load power dissipation
< 0.3 W
Power loss nominal load max.
< 5 W
Rise time
< 0.5 s (UOUT (10 % ... 90 %))
Response time
< 2 ms
Connection in parallel
yes, for redundancy and increased capacity
Connection in series
yes