HCM
S8VK-T12024
Delivery time:3 days.
Power rating | 120 W | |
---|---|---|
Output voltage | 24 VDC | |
Efficiency | 89% typ. (Three-phase 400 VAC input) | |
Input | Rated input voltage |
380 to 480 VAC (Three-phase / two-phase) 450 to 600 VDC |
Allowable input voltage variable range |
340 to 576 VAC (Two-phase)/320 to 576 VAC (Three-phase) 450 to 810 VDC |
|
Frequency | 50/60Hz (47 to 63 Hz) | |
Rated input current | 0.40 A typ. (Three-phase 400 VAC input) | |
Leakage current | 3.5 mA max., 0.70 mA typ. (Three-phase 400 VAC input) | |
Inrush current (cold start at 25 ℃) | 28 A typ. (Three-phase 400 VAC input) | |
Output | Rated output current | 5 A |
Output voltage variable range | 24 to 29.5 VDC With V.ADJ | |
Maximum peak current | 6 A | |
Ripple | 40 mV(p-p) max. | |
Static input variation influence | 0.5% max. | |
Static load variation influence | 1.5% max. | |
Ambient temperature variation influence | 0.05%/℃ max. | |
Start up time | 600 ms typ. (Three-phase 400 VAC input) | |
Hold time | 35 ms typ. (Three-phase 400 VAC input) | |
Additional functions | Overload protection | Yes, automatic reset |
Overvoltage protection | Yes, Shut off the input voltage and turn on the input again | |
Series operation | Yes (Up to 2 Power Supplies with external diode) | |
Parallel operation | Yes (Up to 2 Power Supplies) | |
Output indicator | Yes (LED, color: green, lighting from 80 to 90% or more of rated voltage) | |
Insulation | Dielectric strength |
Between all input terminals and all output terminals: 3 kVAC for 1 min, Cut-off current: 20 mA Between all input terminals and PE terminals: 2.5 kVAC for 1 min, Cut-off current: 20 mA Between all output terminals and PE terminals: 1 kVAC for 1 min, Cut-off current: 30 mA |
Insulation resistance | Between all output terminals and all input terminals/ PE terminals: 100 MΩ min., at 500 VDC | |
Environment | Vibration resistance | 10 to 55 Hz, 0.375 mm single amplitude in each 3 directions for 2 hours |
Shock resistance | 150 m/s2, in each 6 directions 3 times | |
Ambient temperature (Operating) | -40 to 70 ℃ (with no freezing or condensation) | |
Ambient temperature (Storage) | -40 to 85 ℃ (with no freezing or condensation) | |
Ambient humidity (Operating) | 95% max. | |
Ambient humidity (Storage) | 95% max. | |
Reliability | MTBF | 135,000 hours min. |
Construction | Construction | Covered type |
Connection | Terminal blocks | |
Terminal type | Rod terminal | |
Mounting | DIN track mounting | |
Degree of protection | IP20, EN/IEC 60529 | |
Weight (Main) | 650 g max. |