HCM
C63H42D630P
Delivery time:4-6 weeks
Product application
Power distribution protection
Number of poles
4P
product type
Circuit breaker
Neutral wire position
left
Network type
AC
Network frequency
50/60 Hz
Description of protective electrode
4D
Rated current [In]
630 A at 40 ° C above
Rated insulation voltage [Ui]
800 V AC 50/60 Hz according to EN/IEC 60947-2
Rated impulse withstand voltage [Uimp]
8 kV
Rated operating voltage [Ue]
690 V AC 50/60 Hz
Circuit breaker model
H
Breaking capacity
100 kA Icu on... 220/240 V AC 50/60 Hz in accordance with EN/IEC 60947-2
70 kA Icu on... 380/415 V AC 50/60 Hz in accordance with EN/IEC 60947-2
65 kA Icu 440 V AC 50/60 Hz on... according to EN/IEC 60,947-2
50 kA Icu at... 500 V AC 50/60 Hz in accordance with EN/IEC 60947-2
35 kA Icu 525 V AC 50/60 Hz on... according to EN/IEC 60,947-2
20 kA Icu on... 660/690 V AC 50/60 Hz in accordance with EN/IEC 60947-2
Operating breaking capacity [Ics]
100 kA on... 220/240 V AC 50/60 Hz in accordance with EN/IEC 60947-2
70 kA on... 380/415 V AC 50/60 Hz in accordance with EN/IEC 60947-2
65 kA 440 V AC 50/60 Hz on... according to EN/IEC 60947-2
50 kA on... 500 V AC 50/60 Hz according to EN/IEC 60947-2
11 kA 525 V AC 50/60 Hz on... according to EN/IEC 60947-2
10 kA 660/690 V AC 50/60 Hz on... according to EN/IEC 60947-2
Use Category
Class AC
Release name
Micrologic 2.3
Release type
Electronic
Tripper rating
630 A at 40 ° C above
Protection type
Overload protection (long time delay)
Short circuit protection (magnetic protection)
Short circuit short time delay protection
class of pollution
3 Conform to IEC 60664-1
Isolation function
Applicable to EN/IEC 60947-2
Supplementary information
control type
Handle
Rotating handle
Extended rotary handle
Installation type
Plug in
Installation method
Base plate installation
Connection mode - upper end
Front connection
Connection mode - lower end
Front connection
Mechanical life
15000 times
Electrical life
8000 times 440 V AC 50/60 Hz In/2 according to IEC 60947-2
4000 times 440 V AC 50/60 Hz In according to IEC 60947-2
6000 times 690 V AC 50/60 Hz In/2 according to IEC 60947-2
2000 times 690 V AC 50/60 Hz In according to IEC 60947-2
Phase spacing
45 mm
Wiring capacity
4 Screw type terminals 240 mm ² Copper or aluminum for EverLink wiring
Local signal indication
LED ready
LED 90 % Ir
LED 105 % Ir
Contact position indication
have
Neutral line protection setting
Ir
Long time delay current setting type
9 gear adjustable
Setting value of long delay current [Ir]
250…630 A
Setting type of long delay time
Fixed
[tr] Setting range of long delay time
400 s 1.5 x Ir on
16 s 6 x Ir on
7.2 x Ir on... for 11 s
Thermal memory
20 minutes before and after tripping
Setting type of short delay current
9 gear adjustable
Setting value of short delay current [Isd]
1.5...10 x Ir
Setting type of short delay time
Fixed
Setting value of short delay time [tsd]
20 ms
Setting type of instantaneous protection current
Fixed
Instantaneous protection setting value [Ii]
6900 A
Overvoltage category
Class II
height
255 mm
width
185 mm
depth
110 mm