LC1F185F7
1
  • LC1F185F7
2
views: 207

LC1F185F7

Rate:
0.0000/5

( 0 reviews )

Item NO.: V007873 MOQ: 0
Weight:    5kgs
Package Size:  
 Price:
$336.00
 Qty:
      $336.00
 Shipping:   Calculate Shipping Cost

ZZ

LC1F185F7 AC110V

delivery time:6 weeks



Main information
Product range
TeSys
Product range
TeSys F
product type
Contactor
Short product name
LC1F
Contactor application field
Applied to AC load with power factor greater than or equal to 0.95
Applied to non inductive or micro inductive load and resistance furnace
Use Category
AC-1
AC-3
Number of poles
3P
Rated operating voltage [Ue]
<= 460 V DC
<= 690 V AC 50/60 Hz
Control circuit voltage
110 V AC 40...400 Hz
Rated working current [Ie]
275 A 40 ° C) on<=440 V AC-1
185 A 55 ° C) on<=440 V AC-3
Supplementary information
Rated impulse withstand voltage [Uimp]
8 kV
Agreed heating current [Ith]
275 A<40 ° C on
Rated breaking capacity
1480 A acc. to IEC 60947-4-1
Rated short-time withstand current [Icw]
1500 A<40 ° C - 10 s on
920 A<40 ° C - 30 s on
740 A at<40 ° C - 1 minute
500 A at<40 ° C - 3 minutes
400 A at<40 ° C - 10 minutes
Fuses for use with relays
200 A aM on<=440 V
315 A gG on<=440 V
Average impedance
0.33 mΩ - Ith 275 A 50 Hz
Rated insulation voltage [Ui]
1000 V acc. to IEC 60,947-4-1
1500 V acc. to VDE 0110 Group C
Power consumption per pole
12 W AC-3
25 W AC-1
Overvoltage category
III
power pole contact composition
3 NO
Motor power (kW)
90 kW on 380... 400 V AC 50/60 Hz (AC-3)
100 kW on 415 V AC 50/60 Hz (AC-3)
100 kW on 440 V AC 50/60 Hz (AC-3)
110 kW at 500 V AC 50/60 Hz (AC-3)
110 kW on 660... 690 V AC 50/60 Hz (AC-3)
55 kW on 220... 230 V AC 50/60 Hz (AC-3)
33 kW on 400 V AC 50/60 Hz (AC-4)
Control voltage limit
Operation: 0.85... 1.1 Uc 40... 400 Hz 55 ° C)
Release: 0.35... 0.55 Uc 40... 400 Hz 55 ° C)
Mechanical life
10 Mcycles
(~50Hz pull in) Power consumption (VA)
1070 VA, 40...400 Hz 0.9 20 °C)
(~50Hz holding) Power consumption (VA)
9.9 VA, 40...400 Hz 0.9 20 °C)
Maximum operating frequency
2400 times/hour<55 ° C on
Action time
35 ms closed (allowed under Uc)
130 ms breaking (allowed under Uc)
Wiring capacity
Control circuit: bolt fastening 1 cable 1... 4 mm ² Flexible cord without
Control circuit: bolt fastening 2 cable 1... 4 mm ² Flexible cord without
Control circuit: bolt fastening 1 cable 1... 4 mm ² Cord tape
Control circuit: bolt fastening 2 cable 1... 2.5 mm ² Cord tape
Control circuit: bolt fastening 1 cable 1... 4 mm ² Hard wire without
Control circuit: bolt fastening 2 cable 1... 4 mm ² Hard wire without
Power circuit: terminal 2, cable busbar cross-section: 25 x 3 mm
Power circuit: ring terminal 1 cable 150 mm ²
Power circuit: terminal 1 cable 150 mm ²
Power circuit: bolted connection
Tightening torque
Control circuit: 1.2 N.m
Power circuit: 18 N.m
Installation method
Base plate installation
Heat dissipation
8…9.8 W
motor power range
30... 50 kW on 200... 240 V 3-phase
55... 100 kW on 200... 240 V 3-phase
55... 100 kW on 380... 440 V 3-phase
55... 100 kW on 480... 500 V 3-phase
110... 220 kW on 480... 500 V 3-phase
Motor starter type
Direct on-line contactor
Contactor coil voltage
110 V AC standard
Compliance with standards
EN 60947-4-1
IEC 60947-4-1
EN 60947-1
IEC 60947-1
JIS C8201-4-1
Product certification
UL
CSA
ABS
LROS (Lloyds register of shipping)
IEC CB Report
DNV
RINA
RMRoS
BV
UKCA
model
LC1F
Control loop characteristics
AC on 40... 400 Hz
environment
IP protection class
IP2x front panel with protective cover complies with IEC 60529
IP2x front panel with protective cover according to VDE 0106
Protective measures
TH
Operating temperature
-5…55 °C
Storage ambient temperature
-60…80 °C
Ambient air temperature
-40…70 °C
height
174 mm
width
168.5 mm
depth
181 mm
Operating altitude
3000 m without derating
Net weight 
4.65 kg

 
No comment
Total 0 records, divided into1 pages. First Prev Next Last
View History
Related tools
$39.00
$88.00
$1205.00
$346.00
$1162.00
$7.50
$44.00
Business time
9:00-22:00
  • Email:zorx@xaplc.com