zx
Model:ACT20P-PR0DCDII-S
Delivery time:in stock
Signal converter/insulator, 24…230 V AC/DC power supply, Input : I/U universal, Output : I/U universal
Item No.1481970000
Version
|
Signal converter/insulator, 24…230 V AC/DC power supply, Input : I/U universal, Output : I/U universal
|
Order No.
|
1481970000
|
Type
|
ACT20P-PRO DCDC II-S
|
GTIN (EAN)
|
4050118291032
|
Qty.
|
1 ST
Depth
|
113.7 mm
|
Depth (inches)
|
4.476 inch
|
Height
|
119.2 mm
|
Height (inches)
|
4.693 inch
|
Width
|
12.5 mm
|
Width (inches)
|
0.492 inch
|
Net weight
|
130 g
|
Input current
|
configurable
± 0.1mA...± 100 mA
|
Input resistance, current
|
< 5 mA: approx. 100 Ω; >5 mA: approx. 5 Ω
|
Input resistance, voltage
|
approx. 1 MΩ
|
Input signal
|
Voltage source
Current source
|
Input voltage
|
configurable
±40 mV…±300 V
Measuring range. min 40 mV
|
Number of inputs
|
1
|
Sensor
|
4- wire sensor (with own power supply)
|
Cut-off frequency (-3 dB)
|
> 10 kHz/ < 10 Hz
|
Load impedance current
|
≤ 600 Ω
|
load impedance voltage
|
≥ 1 kΩ
|
Offset current
|
20 µA
|
Offset voltage
|
< 10 mV
|
Output current
|
Adjustable
0...±20 mA
|
Output voltage, note
|
Adjustable
0...±10 V
|
Status indicator
|
Green LED
|
Type
|
active (as current source) or passive (as current sink)
connected control can be active / passive
|
Accuracy
|
< 0.05 % of measuring range
|
Configuration
|
DIP switch
or via display and push-buttons
|
Galvanic isolation
|
3-way isolator
between input ⁄ output ⁄ supply
|
Power consumption
|
≤2.3 W
|
Rail
|
TS 35
|
Step response time
|
≤50 µs
|
Temperature coefficient
|
≤0,01% des Messbereichs⁄°C
|
Type of connection
|
Screw connection
|
Voltage supply
|
24…230 V DC ±20 %
24…230 V AC ±10 % @ 48…62 Hz
|
EMC standards
|
EN 60079-0
EN 60079-15
EN 61010-1
EN 61140
EN 61326-1
UL 61010-1
SN29500 for MTBF
|
Galvanic isolation
|
3-way isolator
between input ⁄ output ⁄ supply
|
Impulse withstand voltage
|
5 kV (1.2/50 µs)
|
Insulation voltage
|
4 kVeff
input ⁄ output ⁄ power supply
|
Pollution severity
|
2
|
Rated voltage
|
600 V
|
Surge voltage category
|
II
|
|