C10N32D100   NSX100N
1
  • C10N32D100   NSX100N
2
views: 128

C10N32D100 NSX100N

Rate:
0.0000/5

( 0 reviews )

Item NO.: V008490 MOQ: 0
Weight:    2.1kgs
Package Size:  
 Price:
$198.00
 Qty:
      $198.00
 Shipping:   Calculate Shipping Cost

YYF

C10N32D100  NSX100N MIC2.2 100 3P F

Delivery time: 1-2 weeks


This ComPacT NSX100N is a complete 3P 3d fixed circuit breaker designed to optimize space and breaking capacity. It is an optimal choice for all standard and specific applications. The breaking capacity (Icu) is 50kA rms at 415VAC 50/60Hz. The operational voltage is 690VAC 50/60Hz. This product embeds an electronic MicroLogic 2.2 trip unit, with 100A rating. MicroLogic 2.2 trip unit provides adjustable long time and short time protections, and a fixed instantaneous protection. This 3 poles version (105mm x 161mm x 86mm) comes with a variety of optional functions and accessories. It is compliant with international standards (IEC 60947), CCC, EAC and marine specifications. ComPacT NSX100N is part of Schneider Electric EcoStruxure Power architecture.
----------------------------
Specifications
Main
Range
ComPacT new generation
Product name
ComPacT NSX new generation
Device short name
NSX100N
Product or component type
Circuit breaker
Device application
Distribution
Poles description
3P
Protected poles description
3D
[In] rated current
100 A at 40 °C
[Ue] rated operational voltage
690 V AC 50/60 Hz
Network type
AC
Network frequency
50/60 Hz
suitability for isolation
Yes conforming to EN/IEC 60947-2
Utilisation category
Category A
[Icu] rated ultimate short-circuit breaking capacity
90 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
50 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
36 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
35 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2
10 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Performance level
N 50 kA 415 V AC
Trip unit name
Micrologic 2.2
Trip unit technology
Electronic
Trip unit protection functions
LSoI
Control type
Toggle
Circuit breaker mounting mode
Fixed
Complementary
[Ui] rated insulation voltage
800 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage
8 kV
[Ics] rated service short-circuit breaking capacity
90 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
50 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
50 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
36 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2
35 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2
10 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Mechanical durability
50000 cycles
electrical durability
50000 cycles at 440 V In/2
30000 cycles at 440 V In
20000 cycles at 690 V In/2
10000 cycles at 690 V In
power dissipation per pole
4.7 W
Mounting support
Backplate
Mounting position
Horizontal and vertical
Flat on the back
Upside connection
Front
Downside connection
Front
connection pitch
35 mm
protection type
L : for overload protection (long time)
So : for short time short-circuit protection with fixed delay
I : for instantaneous short-circuit protection
trip unit rating
100 A at 40 °C
Long-time pick-up adjustment type Ir (thermal protection)
Adjustable 9 settings
[Ir] long-time protection pick-up adjustment range
40...100 A
Long-time protection delay adjustment type tr
Fixed
[tr] long-time protection delay adjustment range
400 s at 1.5 x Ir
16 s at 6 x Ir
11 s at 7.2 x Ir
Thermal memory
20 minutes before and after tripping
Short-time protection pick-up adjustment type Isd
Adjustable 9 settings
[Isd] Short-time protection pick-up adjustment range
1.5...10 x Ir
Short-time protection delay adjustment type tsd
Fixed
Instantaneous protection pick-up adjustment type Ii
Fixed
[Ii] instantaneous protection pick-up adjustment range
1500 A
Earth-leakage protection
Without
Zone selective interlocking ZSI
Without
Number of slots for electrical auxiliaries
5 slot(s)
local signalling
Flashing LED (green) for ready to operate
LED 105 % Ir (red) for overload
LED 90 % Ir (orange) for overload
Width (W)
105 mm
Height (H)
161 mm
Depth (D)
86 mm
Product weight
2.05 kg
Environment
Standards
EN/IEC 60947
Product certifications
CCC
EAC
Marine
Overvoltage category
Class II
Electrical shock protection class
Class II
pollution degree
3 conforming to IEC 60664-1
IP degree of protection
IP40 conforming to IEC 60529
IK degree of protection
IK07 conforming to IEC 62262
Ambient air temperature for operation
-25…70 °C
Ambient air temperature for storage
-50…85 °C
relative humidity
0…95 %
operating altitude
0...2000 m without derating
2000 m...5000 m with derating


 