NSX160H 70kA AC 3P3D 150A MA
1
  • NSX160H 70kA AC 3P3D 150A MA
2
views: 208

NSX160H 70kA AC 3P3D 150A MA

Rate:
0.0000/5

( 0 reviews )

Item NO.: V008609 MOQ: 0
Weight:    0kgs
Package Size:  
 Price:
$286.00
 Qty:
      $286.00
 Shipping:   Calculate Shipping Cost

ZZ

NSX160H 70kA AC 3P3D 150A MA

delivery time:in stock



Main information
Product range
ComPacT new generation
Product name
ComPacT NSX new generation
Short product name
NSX160H
product type
Circuit breaker
Product application
Motor protection
Number of poles
3P
Description of protective electrode
3D
Rated current [In]
150 A at 65 ° C above
Rated operating voltage [Ue]
690 V AC 50/60 Hz
Network type
AC
Network frequency
50/60 Hz
Isolation function
Applicable to EN/IEC 60947-2
Use Category
Class AC
[Icu] Rated ultimate short-circuit breaking capacity
100 kA Icu on... 220/240 V AC 50/60 Hz acc. to IEC 60947-2
70 kA Icu on... 380/415 V AC 50/60 Hz acc. to IEC 60947-2
65 kA Icu on... 440 V AC 50/60 Hz acc. to IEC 60947-2
50 kA Icu on... 500 V AC 50/60 Hz acc. to IEC 60947-2
35 kA Icu on... 525 V AC 50/60 Hz acc. to IEC 60947-2
10 kA Icu on... 660/690 V AC 50/60 Hz acc. to IEC 60947-2
Breaking capacity
H 70 kA 415 V AC
Release name
MA
Release type
magnetic
Release protection function
I
control type
Handle
Circuit breaker installation mode
Fixed
Supplementary information
Rated insulation voltage [Ui]
800 V AC 50/60 Hz
Rated impulse withstand voltage [Uimp]
8 kV
[Ics] Rated operating short-circuit breaking capacity
100 kA on 220/240 V AC 50/60 Hz acc. to IEC 60947-2
70 kA on... 380/415 V AC 50/60 Hz acc. to IEC 60947-2
65 kA on... 440 V AC 50/60 Hz acc. to IEC 60947-2
50 kA on 500 V AC 50/60 Hz acc. to IEC 60947-2
35 kA on 525 V AC 50/60 Hz acc. to IEC 60947-2
10 kA on... 660/690 V AC 50/60 Hz acc. to IEC 60947-2
Mechanical life
40000 times
Electrical life
40000 times on 440 V In/2
20000 times on 440 V In
15000 times on 690 V In/2
7500 times 690 V In on
Power consumption per pole
8.55 W
Installation method
Base plate installation
Installation position
Horizontal and vertical direction
Flat on the back
Connection mode - upper end
Front connection
Connection mode - lower end
Front connection
Polar spacing
35 mm
Protection type
I: for short-circuit protection (magnetic protection)
Tripper rating
150 A at 65 ° C above
Setting type of short time delay protection Isd
Adjustable
[Isd] Setting range of short time delay protection threshold
9...14 x In
Setting type of instantaneous overcurrent protection Ii
Adjustable 9 settings
[Ii] Setting range of instantaneous overcurrent protection threshold
9...14 x In
Leakage current protection
No leakage protection
Number of installation slots for electrical accessories
5 grooves
Width
105 mm
High
161 mm
Deep
86 mm
Net weight 
2.2 kg

 