ZLL
2866750
delivery time:1-2 weeks
AC operation | |
Nominal input voltage range | 100 V AC ... 240 V AC |
Input voltage range | 85 V AC ... 264 V AC |
110 V DC ... 350 V DC (typ. 90 V DC (UL 508: ≤ 300 V DC)) | |
Electric strength, max. | 300 V AC |
Voltage type of supply voltage | AC/DC |
Inrush current | < 15 A |
Inrush current integral (I2t) | < 1 A2s |
AC frequency range | 45 Hz ... 65 Hz |
Frequency range DC | 0 Hz |
Mains buffering time | > 55 ms (120 V AC) |
> 55 ms (230 V AC) | |
Current consumption | 1.2 A (120 V AC) |
0.6 A (230 V AC) | |
1.3 A (110 V DC) | |
0.6 A (220 V DC) | |
Nominal power consumption | 145 VA |
Protective circuit | Transient surge protection; Varistor |
Power factor (cos phi) | 0.94 |
Typical response time | < 0.15 s |
Input fuse | 5 A (slow-blow, internal) |
Permissible backup fuse | B6 B10 B16 AC: |
Permissible DC backup fuse | DC: Connect a suitable fuse upstream |
Recommended breaker for input protection | 6 A ... 16 A (AC: Characteristics B, C, D, K) |
Discharge current to PE | < 3.5 mA |