ZLL
LRD16C
delivery time:in stock
Range
TeSys
TeSys Deca
Product name
TeSys LRD
TeSys Deca
Product or component type
Differential thermal overload relay
Device short name
LRD
Relay application
Motor protection
Product compatibility
LC1D18
LC1D38
LC1D32
LC1D12
LC1D25
Network type
DC
AC
thermal overload class
Class 10A conforming to IEC 60947-4-1
Thermal protection adjustment range
9…13 A
[Ui] rated insulation voltage
Power circuit: 600 V conforming to CSA
Power circuit: 600 V conforming to UL
Power circuit: 690 V conforming to IEC 60947-4-1
Network frequency
0...400 Hz
mounting support
Plate, with specific accessories
Rail, with specific accessories
Under contactor
tripping threshold
1.14 +/- 0.06 Ir conforming to IEC 60947-4-1
Auxiliary contact composition
1 NO + 1 NC
[Ith] conventional free air thermal current
5 A for signalling circuit
permissible current
1.5 A at 240 V AC-15 for signalling circuit
0.1 A at 250 V DC-13 for signalling circuit
[Ue] rated operational voltage
690 V AC 0...400 Hz for power circuit conforming to IEC 60947-4-1
associated fuse rating
4 A gG for signalling circuit
4 A BS for signalling circuit
[Uimp] rated impulse withstand voltage
6 kV
phase failure sensitivity
Tripping current 130 % of Ir on two phase, the last one at 0
control type
Red push-button: stop
Blue push-button: reset
Temperature compensation
-20…60 °C
connections - terminals
Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm² flexible without cable end
Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm² flexible with cable end
Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm² solid
Power circuit: screw clamp terminals 1 cable(s) 1.5…10 mm² flexible without cable end
Power circuit: screw clamp terminals 1 cable(s) 1…4 mm² flexible with cable end