ZLL
A9F79332
delivery time:8-12weeks
Device application | Distribution |
---|---|
Range | Acti9 |
Product name | Acti9 iC60 |
Product or component type | Miniature circuit-breaker |
Device short name | IC60N |
Poles description | 3P |
Number of protected poles | 3 |
[In] rated current | 32 A |
Network type |
AC DC |
Trip unit technology | Thermal-magnetic |
Curve code | C |
breaking capacity |
6000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1 36 kA Icu at 12...60 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 20 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 6 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 36 kA Icu at 100...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at <= 180 V DC conforming to EN/IEC 60947-2 |
utilisation category |
Category A conforming to EN 60947-2 Category A conforming to IEC 60947-2 |
suitability for isolation |
Yes conforming to EN 60898-1 Yes conforming to EN 60947-2 Yes conforming to IEC 60898-1 Yes conforming to IEC 60947-2 |
Standards |
IEC 60947-2 EN 60947-2 EN 60898-1 IEC 60898-1 |